E-mail

Acrel AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor

Acrel's dual source AC circuits monitor is ideal for power distribution and circuit protection. The AMC16Z-ZA offers measurement of various electrical parameters, power quality analysis, temperature and humidity monitoring, leakage current detection, and reliable communication through its RS485 interface. With high accuracy and digital output and input channels, this monitor is a must-have for any AC circuits monitoring need.

electrical distribution system protection
electrical distribution system protection
electrical power protection
electrical power system protection
electrical protection system
Products

Specifications of AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor

Function Overview
Main Parameters
Environment
FunctionDescription
Measurement
(Common)
Three-phase AC kWh, kVarh, Active Power, Reactive Power, Current, Voltage, Power Factor, Apparent Power, Frequency, Zero ground voltage, neutral line current
Measurement
(Power Quality)
total harmonic content (THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest coefficient (CF), telephone waveform factor (THFF), peak voltage, voltage, and current sequence quantity
Temp.&Humidity MonitoringTemperature Monitoring Range: -40℃~+99℃
Humidity Monitoring Range: 20%~90%
Leakage Current2-channel Leakage Current Measurement
AccuracyElectrical Parameter Metering Accuracy: Voltage/current level 0.2, active power/electric energy level 0.5, reactive power/electric energy level 1
Temperature Metering Accuracy: ±1℃;  Temperature Metering Accuracy: ±5%
CommunicationRS485 Interface (MODBUS-RTU protocol)
DO
(Switch Output)
2-channel DO (Digital Output); 3A 250VAC/3A 30VDC
DI
(Switch Input)
6-channel DI (Digital Input); dry contact


ParameterDescription&Value
Voltage InputRated Voltage3x220~264Vac L-N
Reference Frequency45~65Hz
Current InputRated Current3x1(6)A AC (via CTs)
Power SupplySource fromVoltage Input (Voltage signal input for both measurement and power supply)
InstallationDIN-rail35mm standard DIN-rail Installation
Phase Wiring3P4W3-phase 4-wire
SafetyInsulationAll terminals and the insulation resistance between the conductive pieces not less than 100MΩ
Withstand voltageA-way voltage and current signal, B-way voltage and current signal,  switch output and other ports should meet AC2kV 1min in pairs, the switch input and other ports should meet ac0.5kv 1mim, leakage current should be less than 2mA, no breakdown or flashover


ConditionDescription&Value
TemperatureOperating Temperature: -20℃~+55℃;  Storage Temperature: -40°C ~+70°C
Humidity≤95%RH, no condensation, without corrosive gas
Altitude≤ 2000m


Diagrams of AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor

Diagrams of AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor
Product Features
Diagrams of AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor
Application in Data Center
Diagrams of AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor
Wiring Illustration PIN Overview
Diagrams of AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor
Wiring Diagram
Diagrams of AMC16Z-ZA AC A+B Dual Source AC Circuits Monitor
Dimension
Innovation, Efficiency, Unity, Integrity.
Acrel, your reliable energy meter partner. Don't hesitate to contact us!
Contact Us
Related AMC Series Data Center Monitor Module
+8618795636361 michelle.zhou@email.acrel.cn
No. 9 Xincheng Road, Chengjiang Street, Jiangyin City, Jiangsu Province, China.