Abstract: This article introduces the application of “Acrel” DJSF1352-RN DC meter in the UPS metering system. It is mainly used for the measurement of the output energy in the UPS system, and the measurement, communication and control of the circuit system through the Hall sensor.


1. Project Overview

The company is a battery production company, mainly engaged in the production and supply of industrial batteries and UPS. The customer needs to use a DC meter for monitoring and measuring the electrical energy at the output of the UPS.


2. DJSF1352-RN DC Energy Meters

    DJSF1352-RN rail-mounted DC power meter designed for telecommunications base stations, DC charging piles, solar photovoltaic and other applications, this series of meters can measure the voltage, current, power and forward and reverse energy and so on in the DC system.The actual use of the site, you can measure the total power, but also measure the energy within a specified period of time. The test results can be used for local display, but also with industrial control equipment, computers to form a measurement and control system.

    The meter can have infrared communication interface and RS-485 communication interface, and supports Modbus-RTU protocol and DLT645-97 (07) protocol at the same time.The meter can have relay alarm output and digital input function;You can set the ratio, alarm, and communication through the meter panel keys according to different requirements.The meter can have event recording of switch (Modbus protocol), programming and event setting records (645 protocol), instantaneous and timing freeze function of data (645 protocol), maximum and minimum value recording function of voltage and current power.


3. Type and Function Description

1714984692573.jpg


Note:when dual DC input(D)function is selected,if Hall current sensor input is used in current channel, a power supply module shall be provided to supply power to the second Hall sensor; if D function is not provided, the built-in power supply of electric meter can be used.


Technical parameters

Index

Input

Nominal value

Voltage input range

Current input

DC 0-1000V

Hall sensor:0-20mA、4-20mA、0-5V,0-10V and so on.

Overload

1.2 times rated (continuous); 2 times rated/1 second;

Power consumption

Voltage: ≤0.2VA, current ≤0.1VA

Accuracy class

Class 1

Function

Display

8-bit segment LCD screen (LCD)

Communication Interface

RS485(two options)

Communication protocol

Modbus-RTU,DL/T 645-2007

Switch

Switch output

2 Relay outputs, 2A/30VDC or 2A/250VAC

Switch input

2 dry contact inputs

Pulse output

A second pulse output, a energy pulse output

See the SYS->PLUS display in the meter menu settings. For example: The meter displays 100, which is 100imp/kWh

Power Supply

Voltage range

AC/DC 85-265V or DC24V(±10%) or DC48V(±10%)


Power consumption

≤ 3W

Power frequency withstand voltage

Power supply // Voltage input // Current input // Relay output and switch input // Communication interface / / Pulse output 3kV/1min

Power supply // Relay output // Voltage input // Current input 3kV/1min

Pulse output // Communication interface // Switch input 2kV/1min

Impulse withstand voltage

±6KV

Insulation resistance

≥ 40M Ω

Average barrier-free working hours

≥50000h

Environment

Temperature

Normal operating temperature: -25 °C ~ +65 °C; Limit working temperature: -40 °C ~ +70 °C;

Storage temperature: -40℃~+80℃

Humidity

≤93%RH, no condensation, no corrosive gas

Altitude

≤2500m


4. Customer Requirements

The customer wants to measure the actual output power of the UPS to calculate the conversion ratio of UPS energy storage to energy consumption. The UPS input end uses our ADL series electric meter, the output end uses DJSF1352-RN DC meter, and the electrical signal is taken through the shunt in order to achieve the purpose of output measurement.





Recommended Acrel Energy Meter and Related Products
Other Projects of Acrel Energy Meter and Related Products
+8618795636361 michelle.zhou@email.acrel.cn