Acrel AGF-M Solar PV DC String Monitoring Device

AGF-M solar PV DC string monitoring device is specially used in the intelligent photovoltaic confluence box to monitor the operating state of the photovoltaic cell array. It can measure the photovoltaic cell current, collect the state of the lightning protection device in the confluence box and collect the state of the DC circuit breaker and the relay contact output. With sensor interfaces such as wind speed, temperature, and irradiance meter, the device has an RS485 interface to upload the measured and collected data and equipment status.

dc combiner box with string monitoring
dc combiner box with string monitoring
solar energy monitoring device
solar energy monitors
solar generation meter monitoring
solar inverter remote monitoring
Products

Specification of AGF-M Solar PV DC String Monitoring Device

Parameters

Item

AGF-M4T

AGF-M8T

AGF-M12T

AGF-M16T

AGF-M20T

AGF-M24T

Input channels

4

8

12

16

20

24

Rated current

DC 0~20A

Response time

1s

Accuracy

0.5 class

Temperature coefficient

400ppm

RS485 communication

RS485/Modbus-RTU protocol, 4800/9600/19200/38400bps

Additional function

Switch input

3-way input(optocoupler or dry contact mode)

General technical parameters


Temperature/ Humidity

Working temperature: -35~+65℃, humidity95%,no condensation, no corrosion gas place

*Display module work temperature: -20~+70℃

Temperature measurement function

To measure the inner temperature of the box (-20℃~100℃)

Altitude

≤3000m

Insulation resistance

≥100MΩ


Industrial frequency withstand voltage

power/communication/switching input/cell voltage input--AC 2kV/1min

(When the auxiliary power supply is DC1500V, the withstand voltage between the power supply, photocell input and other circuits is AC 2.7kV)

Current input/powercell voltagecommunicationswitching

state—AC3.5kV/1min

EMC

GB_T 17626.2-2006;

Electrostatic discharge immunity test 3rd grade, air discharge 8kV, contact discharge 6kV.

GB_T 17626.4-2008;

Electrical fast transient immunity test grade 4, common mode 4kV, difference mode 2kV

GB_T 17626.5-2008;

Surge(shock) immunity test grade 4, common mode 4kV, difference mode 2kV

GB_T 17626.8-2006;

Power frequency magnetic field immunity test grade 4


Features of AGF-M Solar PV DC String Monitoring Device

01

It has a relay output, which can be set as a jog mode, used to drive the automatic opening and closing of the DC circuit breaker;

02

The on-site digital tube displays the input current of each channel in a cycle, and has an automatic shutdown energy-saving display mode;

03

It can be equipped with dual-channel RS485 interface, supports ModbusRTU communication protocol, and the communication address, baud rate, and data mode can be set freely.

Diagram of AGF-M Solar PV DC String Monitoring Device

Diagram of AGF-M Solar PV DC String Monitoring Device
Features
Diagram of AGF-M Solar PV DC String Monitoring Device
Features
Diagram of AGF-M Solar PV DC String Monitoring Device
Features
Diagram of AGF-M Solar PV DC String Monitoring Device
Features
Diagram of AGF-M Solar PV DC String Monitoring Device
Features
Diagram of AGF-M Solar PV DC String Monitoring Device
Features
Diagram of AGF-M Solar PV DC String Monitoring Device
Features
Diagram of AGF-M Solar PV DC String Monitoring Device
Wiring Instruction
Diagram of AGF-M Solar PV DC String Monitoring Device
Installation Instruction
Diagram of AGF-M Solar PV DC String Monitoring Device
Installation Instruction
Diagram of AGF-M Solar PV DC String Monitoring Device
Practical Application
Diagram of AGF-M Solar PV DC String Monitoring Device
Practical Application
Diagram of AGF-M Solar PV DC String Monitoring Device
Practical Application
Innovation, Efficiency, Unity, Integrity.
Acrel, your reliable energy meter partner. Don't hesitate to contact us!
Contact Us
Related DC Energy Meter
+8618795636361 michelle.zhou@email.acrel.cn
No. 9 Xincheng Road, Chengjiang Street, Jiangyin City, Jiangsu Province, China.