ADW210 is mainly used for various three-phase power parameter measurement and active and reactive power measurement of low-voltage network. At the same time, the current input of no more than four circuits can be selected. It has RS485 communication and 470MHz wireless communication functions. It can also cooperate with various expansion modules. It is convenient for users to monitor, collect and manage electricity consumption. It can be flexibly installed in the distribution box to realize sub-item electric energy measurement, statistics and analysis for different areas and different loads.


adw210
adw210
electric meter wifi
electricity consumption meter wifi
energy consumption meter wifi
energy meter monitoring over iot
Products

Specification of ADW210 IoT Multi-Circuit Energy Meter

Prototype Function
Expanded Module Function
Technical Parameters (Prototype/Main Body)
Technical Parameters (Paired Current Transformer)
FunctionDescription
Energy MeasurementkWh (positive and negative)
vary (positive and negative)
A, B, C three-phase positive kWh
Electric ParameterU, I, P, Q, S, PF, Hz
Harmonic2-31st voltage and current harmonic
CommunicationRS485 (MODBUS-RTU); baud rate 1200~38400
Key Programming4 keypads to set communication and parameters
DisplayLCD display, 8-digit
LED AlarmOver-voltage, over-current, interruption phase
Data LogMaximum demanded kWh and the time it happened.
SOEup to 200 pcs, record the on-off status of DO/DI
Pulse OutputActive optocoupler pulse output with open collector
Multi-rate/Tariff4 time zones & 12 time periods


Expanded ModuleDescription
AWT100
Communication
Module
4G (Global general module)
2G
LoRaWAN (868 MHz, 923MHz)
LoRa (460~510 MHz)
NB-IoT
-MK
Switch
Module
12 × DI (input)Dry contact input with built-in power supply
4 × DO (output)Relay normally open contact output; rating AC 250V/3A ,DC 30V/3A
Power SupplyDC 12V;consumption:≤1W;RJ45 interface
CommunicationRJ45 interface; MODBUS-RTU (communication with the main body)
-MTC
Temperature
&
Residual Current
Temperature Measurement-20℃~+100℃
Residual Current Measurement10~3000 mA
AccuracyTemperature: ± 2℃; Residual Current: 1% (Class 1)
MeasuringPower SupplyDC 12V; consumption:≤1W; RJ45 interface
ModuleCommunicationRJ45 interface; MODBUS-RTU (communication with the main body)


ParametersDescription
InputVoltageAC 3×220V/380V
Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s
Power consumption:≤ 0.5VA
CurrentAC 5A, 100A400A600A; (external open-type CT)
Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s
Power consumption:≤ 0.5VA
Frequency45~65Hz
Measuring
Accuracy
Voltage&CurrentClass 0.5
Active PowerClass 1
Reactive PowerClass 2
Frequency0.05Hz
2~31st harmonic± 1%
Auxiliary PowerAC/DC 85~265V;consumption≤10VA;
EMCBetter than grade 3
SafetyWithstand Voltage>AC 2000V/1min
Insulation Resistance>100MΩ
EnvironmentWorking Temperature-20℃~+60℃
Storage Temperature-40℃~+70℃
Humidity≤95% (No condensation)
Altitude≤2500m
Paired CTPrimary CurrentSecondary CurrentAperture(Hole size)Accuracy Class
AKH-0.66/K-φ10N5A1.25mA10mmClass 0.5
AKH-0.66/K-φ16N100A20mA16mmClass 0.5
AKH-0.66/K-φ24N400A100mA24mmClass 0.5
AKH-0.66/K-φ36N600A100mA36mmClass 0.5
AKH-0.66-L-45///Class 1
(for residual current)


Features of ADW210 IoT Multi-Circuit Energy Meter

01

Auxiliary functions can be extended through its RJ45 interface to realize DI, DO, temperature measurement, residual current measurement, and 2G, 4G, LoRa, LoRaWan, NB-Lot wireless communication functions;


02

It can be connected to Acrel cloud platform to realize intelligent management;

03

It can directly or indirectly measure parameters such as voltage, current, power, power factor, phase angle, unbalance degree, and harmonics.

Diagram of ADW210 IoT Multi-Circuit Energy Meter

Diagram of ADW210 IoT Multi-Circuit Energy Meter
Features
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Features
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Features
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Features
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Features
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Display Sample
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Wiring Illustration
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Wiring Illustration
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Wiring Illustration
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Wiring Illustration
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Installation Instruction
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Typical Networking Connection
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Typical Networking Connection
Diagram of ADW210 IoT Multi-Circuit Energy Meter
Typical Networking Connection

Video of ADW210 IoT Multi-Circuit Energy Meter

Innovation, Efficiency, Unity, Integrity.
Acrel, your reliable energy meter partner. Don't hesitate to contact us!
Contact Us
Related ADW Series IoT Power Meter
+8618795636361 michelle.zhou@email.acrel.cn
No. 9 Xincheng Road, Chengjiang Street, Jiangyin City, Jiangsu Province, China.